chillii® Cooling Kits HLC

  • Cooling capacity: 105 – 4600 kW /30 – 1300 usRT

  • Working pair: Water/LiBr

  • COP (nominal): 0.80 – 0.83

  • Heat source: Hot water   (70  – 95 °C / 158 – 203 °F)

General

Our LiBr absorption cooling systems are available with a nominal cooling capacity of 105 kW to 4.6 MW. These systems are suitable for applications with cold water temperatures above 5 ° C. With a cooling capacity of up to 4.6 MW, applications for air conditioning and process cooling on an industrial scale are also suitable. The additional electrical power consumption is less than 2 % of the cooling capacity.

Technical Data

Cold water circuit (consumer) 
Temperature range (FF) 5 °C to 15 °C
Nominal temperatures (RF/FF) 13/8 °C
Nominal capacity range 105 kW to 4600 kW
Drive circuit (heat supply)
Temperature range (FF) 70 °C to 95 °C
Nominal temperatures (RF/FF) 95/80 °C
Nominal capacity range 128 kW to 5560 kW